TD-150: Difference between revisions
→Installation of the configurator and connection to the sensor
| Line 112: | Line 112: | ||
If you use C200M2 on Windows 10 and 11 operating systems, drivers should be installed automatically from Windows Update, on the Windows 7 operating system and below, you may need to [https://windowsreport.com/driver-signature-enforcement-windows-10/ disable the electronic signature of drivers] and manually install [https://www.fmeter.ru/download/_ftp/eng/escort_c-200m/Escort%20driver%20C-200M2.zip?v=050623134319 drivers for the С200M2]. | If you use C200M2 on Windows 10 and 11 operating systems, drivers should be installed automatically from Windows Update, on the Windows 7 operating system and below, you may need to [https://windowsreport.com/driver-signature-enforcement-windows-10/ disable the electronic signature of drivers] and manually install [https://www.fmeter.ru/download/_ftp/eng/escort_c-200m/Escort%20driver%20C-200M2.zip?v=050623134319 drivers for the С200M2]. | ||
If the driver was installed correctly, then after connecting the converter to your PC/laptop, you will see the STMicroelectronics Virtual COM Port ('''1''')(C200M) or USB-SERIAL CH341A ('''2''')(C200M2) device in the COM and LPT ports section of the Windows device manager " to enter this menu, press '''win+r''' and enter '''devmgmt.msc''' and press '''OK''' ('''3''') and then expand the com ports submenu ('''4''')" | |||
The com port number displayed in this menu is also needed to connect the sensor. | |||
[[Файл:Ком порты С200М и С200М2.png|900x900пкс]] | [[Файл:Ком порты С200М и С200М2.png|900x900пкс]] | ||
After connecting the converter, sensor to it and checking the installation of drivers by checking the com port number of the converter, you need to open the configurator, select the desired com port which we could find in the device manager ('''1''') and press the '''FLS''' button ('''2'''). | |||
[[Файл:Выбор ком порта и ДУТ.png|750x750пкс]]<blockquote> | [[Файл:Выбор ком порта и ДУТ.png|750x750пкс]]<blockquote>The connection to the FLS should be made '''within 15 seconds after the sensor has been connected''' to power, if the sensor operating mode has been changed from RS-485 to any other. </blockquote>After connecting the sensor you should see this menu: | ||
[[Файл:Описание основного меню конфигуратора на ПК, проводного дут .png]] | [[Файл:Описание основного меню конфигуратора на ПК, проводного дут .png]] | ||
# | # Sensor serial number | ||
# | # Sensor firmware version (FW) | ||
# | # Sensor temperature | ||
# | # Current sensor level | ||
# | # Current CNT level (raw level value) of the sensor | ||
# | # LLS network addresses connected to this converter (if there is more than one address in this list, it means either more than one sensor is connected to the line at the same time or there is interference on the line, in this case it is necessary to check the connection to the FLS for the presence of other conflicting devices and it is necessary to close other programs using the com ports for example tracker configurator) | ||
# | # Network address of the polled sensor (This address is used when connecting in RS485 mode) | ||
# | # Current sensor operating mode | ||
# | # Current range of output values (1-1023 or 1-4095) | ||
# | # Current filtration type and degree | ||
# | # Connected sensor model | ||
== '''<big> | == '''<big>Sensor calibration</big>''' == | ||
[[Файл:Калибровка дут на ПК.gif]] | [[Файл:Калибровка дут на ПК.gif]] | ||
After you have lengthened or shortened the sensor tubes, you need to carry out the sensor calibration procedure. | |||
To do this you need: | |||
* | * Go to menu '''"Sensor calibration"''' | ||
[[Файл:Переход в меню калибровки датчика ПК.png]] | [[Файл:Переход в меню калибровки датчика ПК.png]] | ||
* | * Insert the centralizer into the tubes | ||
* | * Fill the tubes with fuel (by sealing the drain holes with duct tape and filling the tubes, turning the sensor upside down, or submerging the sensor tubes completely in fuel) | ||
* | * Wait for the CNT level to stabilize ('''1''') | ||
* | * Deselect the '''"Calibration without fuel'''" slider ('''2''') | ||
* | * Click '''"Full"''' ('''3''') | ||
* | * The value '''"Full"''' ('''4''') should change to a value close to the value of the current CNT ('''1'''), but not equal to it, since this value is set according to the temperature compensation of the sensor | ||
[[Файл:Калибровка полного ПК.png]] | [[Файл:Калибровка полного ПК.png]] | ||
| Line 162: | Line 162: | ||
</gallery> | </gallery> | ||
* | * Empty the pipes of fuel, leave the centralizer in the pipes | ||
* | * Wait for CNT to stabilize (1) | ||
* | * Click '''"Empty"''' ('''2''') | ||
* | * The value '''"Empty"''' ('''3''') should change to a value close to the value of the current CNT ('''1'''), but not equal to it, since this value is set according to the temperature compensation of the sensor | ||
* | * Click '''"OK"''' | ||
[[Файл:Калибровка пустого ПК.png]] | [[Файл:Калибровка пустого ПК.png]] | ||
* | * The sensor level should display as 1, the sensor calibration process is complete. | ||
Thus, CNT should increase as the sensor tubes fill with fuel. It should change from a value close to the Empty calibration value to the Full calibration value. | |||
[[Файл:CNT_уровень_и_фактический_уровень_топлива.png|854x854пкс]]<blockquote>'''<big> | [[Файл:CNT_уровень_и_фактический_уровень_топлива.png|854x854пкс]]<blockquote>'''<big>ATTENTION! UNBLOCK THE DRAINAGE HOLES AFTER CALIBRATION!!!</big>'''</blockquote>[[Файл:Разблокировка_дренажных_отверстий.png|726x726пкс]] | ||
== '''<big>Калибровка без топлива</big>''' == | == '''<big>Калибровка без топлива</big>''' == | ||