TD-600: Difference between revisions
→Sensor calibration
| Line 492: | Line 492: | ||
* Go to the '''"Settings"''' menu | * Go to the '''"Settings"''' menu | ||
[[ | [[File:Wired mobile settings button.png|frameless|688x688px]] | ||
* Insert the centralizer into the tubes | * Insert the centralizer into the tubes | ||
| Line 501: | Line 501: | ||
* The value '''"Full"''' ('''4''') should change to a value close to the value of the current CNT ('''2'''), but not equal to it, since this value is set according to the temperature compensation of the sensor | * The value '''"Full"''' ('''4''') should change to a value close to the value of the current CNT ('''2'''), but not equal to it, since this value is set according to the temperature compensation of the sensor | ||
[[ | [[File:Wired mobile settings page.png|frameless|456x456px]] | ||
[[ | [[File:Centralizer-Centrator.png|none|thumb|546x546px|'''<big>Centrator</big>''']] | ||
[[ | [[File:Centralizer.png|none|thumb|512x512px|'''<big>Centrator on the tubes</big>''']] | ||
<gallery widths="350" heights="300"> | <gallery widths="350" heights="300"> | ||
Файл:Закрытие дренажных отверстий, переворачивание датчика и заполнение трубок топливом.png|'''<big>Закрытие дренажных отверстий, переворачивание датчика и заполнение трубок топливом</big>''' | Файл:Закрытие дренажных отверстий, переворачивание датчика и заполнение трубок топливом.png|'''<big>Закрытие дренажных отверстий, переворачивание датчика и заполнение трубок топливом</big>''' | ||
| Line 514: | Line 514: | ||
* The value '''"Empty"''' ('''4''') should change to a value close to the value of the current CNT ('''2'''), but not equal to it, since this value is set according to the temperature compensation of the sensor | * The value '''"Empty"''' ('''4''') should change to a value close to the value of the current CNT ('''2'''), but not equal to it, since this value is set according to the temperature compensation of the sensor | ||
[[ | [[File:Mobile configurator Empty set.jpg|frameless]] | ||
Thus, '''CNT''' should increase as the sensor tubes fill with fuel. It should change from a value close to the '''Empty''' calibration value to the '''Full''' calibration value. | Thus, '''CNT''' should increase as the sensor tubes fill with fuel. It should change from a value close to the '''Empty''' calibration value to the '''Full''' calibration value. | ||
[[ | [[File:TankEmptyFull.png|frameless|512x512px]]<blockquote>'''<big>ATTENTION! UNLOCK THE DRAINAGE HOLES AFTER CALIBRATION!!!</big>'''</blockquote>[[File:Unblocking drain holes.png|frameless|726x726px]] | ||
== '''<big>Calibration without fuel</big>''' == | == '''<big>Calibration without fuel</big>''' == | ||
| Line 525: | Line 525: | ||
In this case, make sure that the sensor tubes are empty, there is no fuel in them, but the centralizer must be inserted into the tubes. Leave the '''"Calibrate without fuel"''' switch ('''1''') active ('''green''') and press '''"Calibrate"''' ('''2''') . The values above the Empty and Full buttons will change automatically. | In this case, make sure that the sensor tubes are empty, there is no fuel in them, but the centralizer must be inserted into the tubes. Leave the '''"Calibrate without fuel"''' switch ('''1''') active ('''green''') and press '''"Calibrate"''' ('''2''') . The values above the Empty and Full buttons will change automatically. | ||
[[ | [[File:Wired calibration with fuel mobile.png|frameless]] | ||
If you calibrate the sensor without fuel, the operating range may change slightly. | If you calibrate the sensor without fuel, the operating range may change slightly. | ||