TD-150: Difference between revisions
→Setting the mode, range and network address
| Line 266: | Line 266: | ||
=== '''<big>Setting the mode</big>''' === | === '''<big>Setting the mode</big>''' === | ||
In the main menu, you can change the operating mode of the sensor. The name of the mode coincides with the interface that is used to physically connect the sensor to the GPS | In the main menu, you can change the operating mode of the sensor. The name of the mode coincides with the interface that is used to physically connect the sensor to the GPS tracker | ||
Select the mode you need('''1''') and click '''“Save parameters to device”'''('''2''') | Select the mode you need('''1''') and click '''“Save parameters to device”'''('''2''') | ||
| Line 272: | Line 272: | ||
[[File:Wire mode settings.png|frameless|572x572px]] | [[File:Wire mode settings.png|frameless|572x572px]] | ||
- '''Passive RS485''' should be selected when you plan to connect to line A and B of the | - '''Passive RS485''' should be selected when you plan to connect to line A and B of the tracker's RS-485 interface. The tracker must have the function of polling sensors, for example, requesting information from them. The tracker must be able to interrogate sensors in accordance with the '''LLS protocol'''. | ||
- '''Frequency mode''' is used when connecting to a GPS | - '''Frequency mode''' is used when connecting to a GPS tracker to inputs that can receive and read signals in the range '''300 Hz … 1323 Hz''' or '''300 Hz … 4395 Hz'''. | ||
- '''Active RS485''' mode should be used if the | - '''Active RS485''' mode should be used if the tracker has an RS-485 connection interface, but cannot independently poll the sensor, for example, request information from it; the sensor will send its readings independently every 2 seconds.<blockquote>'''<big>Note: The analog output of the TD-150 is always active on the green wire in the 0.2-9V range, there is no need to turn it on separately</big>'''</blockquote> | ||
=== '''<big>Setting the range</big>''' === | === '''<big>Setting the range</big>''' === | ||
| Line 289: | Line 289: | ||
=== '''<big>Setting the network address</big>''' === | === '''<big>Setting the network address</big>''' === | ||
The default network address of the sensor is 1; if more than one unit is installed or other LLS devices are added, the network address on the sensor may need to be changed. The network address of each sensor must also be specified in the settings of the receiving device ( | The default network address of the sensor is 1; if more than one unit is installed or other LLS devices are added, the network address on the sensor may need to be changed. The network address of each sensor must also be specified in the settings of the receiving device (gps tracker).<blockquote>'''<big>Attention!!! There cannot be two devices with the same network address on the same line; this will cause a conflict.</big>'''</blockquote>To change the network address, enter a new address in the range '''0-255''' in the '''“Change network address”''' field ('''1''') and click '''“Save the parameters to device”''' ('''2'''), after which the configurator should switch to the new sensor address and display the new sensor address in the field '''"Available units"''' ('''3''') and '''"Poll network address"''' ('''4'''). | ||
[[File:Wired before changing Network address.png|none|thumb|611x611px|'''<big>Before changing network address</big>''']] | [[File:Wired before changing Network address.png|none|thumb|611x611px|'''<big>Before changing network address</big>''']] | ||
[[File:After changing network address.png|none|thumb|614x614px|'''<big>After changing network address</big>''']] | [[File:After changing network address.png|none|thumb|614x614px|'''<big>After changing network address</big>''']] | ||
| Line 568: | Line 568: | ||
=== '''<big>Setting the mode</big>''' === | === '''<big>Setting the mode</big>''' === | ||
In the main menu, you can change the operating mode of the sensor. The name of the mode coincides with the interface that is used to physically connect the sensor to the GPS | In the main menu, you can change the operating mode of the sensor. The name of the mode coincides with the interface that is used to physically connect the sensor to the GPS tracker | ||
Go to Settings | Go to Settings | ||
| Line 580: | Line 580: | ||
[[File:Wired set parameters mobile.png|frameless|798x798px]] | [[File:Wired set parameters mobile.png|frameless|798x798px]] | ||
- '''Passive RS485''' should be selected when you plan to connect to line A and B of the | - '''Passive RS485''' should be selected when you plan to connect to line A and B of the tracker's RS-485 interface. The tracker must have the function of polling sensors, for example, requesting information from them. The tracker must be able to interrogate sensors in accordance with the '''LLS protocol'''. | ||
- '''Frequency mode''' is used when connecting to a GPS | - '''Frequency mode''' is used when connecting to a GPS tracker to inputs that can receive and read signals in the range '''300 Hz … 1323 Hz''' or '''300 Hz … 4395 Hz''' | ||
- '''Active RS485 mode''' should be used if the | - '''Active RS485 mode''' should be used if the tracker has an RS-485 connection interface, but cannot independently interrogate the sensor, for example, request information from it; the sensor will send its readings independently every 2 seconds.<blockquote>'''<big>Note: The analog output of the TD-150 is always active on the green wire in the 0.2-9V range, there is no need to turn it on separately</big>'''</blockquote> | ||
=== '''<big>Setting the range</big>''' === | === '''<big>Setting the range</big>''' === | ||
| Line 599: | Line 599: | ||
=== '''<big>Setting the network address</big>''' === | === '''<big>Setting the network address</big>''' === | ||
The default network address of the sensor is 1; if more than one unit is installed or other LLS devices are added, the network address on the sensor may need to be changed. The network address of each sensor must also be specified in the settings of the receiving device ( | The default network address of the sensor is 1; if more than one unit is installed or other LLS devices are added, the network address on the sensor may need to be changed. The network address of each sensor must also be specified in the settings of the receiving device (gps tracker).<blockquote>'''<big>Attention!!! There cannot be two devices with the same network address on the same line; this will cause a conflict.</big>'''</blockquote>To change the network address, enter a new address in the range '''0-255''' in the '''“Network address”''' field ('''1''') and click “'''Set parameters'''” ('''2''') | ||
[[File:Wired setting address.png|frameless|501x501px]] | [[File:Wired setting address.png|frameless|501x501px]] | ||
| Line 756: | Line 756: | ||
'''Attention!''' By default, there is no password set on the sensor! If you connected the sensor and a password was already set on it, contact technical support.. | '''Attention!''' By default, there is no password set on the sensor! If you connected the sensor and a password was already set on it, contact technical support.. | ||
= '''<big>Connecting the sensor to the GPS | = '''<big>Connecting the sensor to the GPS tracker</big>''' = | ||
== '''<big>General instructions</big>''' == | == '''<big>General instructions</big>''' == | ||
| Line 770: | Line 770: | ||
== '''<big>Connection diagrams</big>''' == | == '''<big>Connection diagrams</big>''' == | ||
In order to connect the sensor to the GPS | In order to connect the sensor to the GPS tracker and to the power source, use the diagram presented below. | ||
[[File:Wired RS-485 no R.png|none|thumb|512x512px|'''<big>RS-485 connection diagram</big>''']] | [[File:Wired RS-485 no R.png|none|thumb|512x512px|'''<big>RS-485 connection diagram</big>''']] | ||
[[File:Wired Frequency mode.png|none|thumb|512x512px|'''<big>Wiring diagram for Frequency output</big>''']] | [[File:Wired Frequency mode.png|none|thumb|512x512px|'''<big>Wiring diagram for Frequency output</big>''']] | ||
| Line 870: | Line 870: | ||
* If you cannot complete the firmware, contact our technical support | * If you cannot complete the firmware, contact our technical support | ||
== '''<big>Checking the connection between the sensor and the | == '''<big>Checking the connection between the sensor and the tracker via RS-485</big>''' == | ||
If the sensor, for some reason, after you have configured everything correctly, does not transmit data to the | If the sensor, for some reason, after you have configured everything correctly, does not transmit data to the tracker, you need to find out whether data is being exchanged between devices. | ||
To do this, connect the sensor to the | To do this, connect the sensor to the tracker via RS-485. Connect power to both devices. | ||
After that, take the RS-485-USB converter and connect it between the sensor and the | After that, take the RS-485-USB converter and connect it between the sensor and the tracker as shown below: | ||
For RS-485, lines A and B of the converter must be connected to lines A and B of the sensor | For RS-485, lines A and B of the converter must be connected to lines A and B of the sensor | ||
| Line 920: | Line 920: | ||
= '''<big>Remote control of FLS Escort</big>''' = | = '''<big>Remote control of FLS Escort</big>''' = | ||
At the moment, Navtelecom and GlonassSoft | At the moment, Navtelecom and GlonassSoft trackers have the ability to configure wired Escort FLS by remotely connecting to the gps tracker without using the above commands. This can be done according to these instructions: | ||
'''[https://www.youtube.com/watch?v=qmU9DQCO4Fc Smart and Signal, built-in configurator]''' | '''[https://www.youtube.com/watch?v=qmU9DQCO4Fc Smart and Signal, built-in configurator]''' | ||
| Line 928: | Line 928: | ||
'''[https://youtu.be/rFzWX8E97Bg UMKa]''' | '''[https://youtu.be/rFzWX8E97Bg UMKa]''' | ||
It is also possible to send commands via SMS commands or tracker | It is also possible to send commands via SMS commands or tracker tracker. | ||
At the moment, we know that the remote control function is supported by trackers of the Smart and Signal family produced by Navtelecom (Signal, Smart), Technocom (AvtoGRAPH) and GlonassSoft (UMKa). Transmission of commands to the sensor is possible only in RS-485 operating mode. | At the moment, we know that the remote control function is supported by trackers of the Smart and Signal family produced by Navtelecom (Signal, Smart), Technocom (AvtoGRAPH) and GlonassSoft (UMKa). Transmission of commands to the sensor is possible only in RS-485 operating mode. | ||
| Line 946: | Line 946: | ||
# Specify the parameters that need to be changed by this command | # Specify the parameters that need to be changed by this command | ||
# Click on the '''Generate''' button | # Click on the '''Generate''' button | ||
# Then you need to send the selected part of the command via the tracker configurator or by SMS message to the number of the current SIM card of this GPS | # Then you need to send the selected part of the command via the tracker configurator or by SMS message to the number of the current SIM card of this GPS tracker | ||
ATTENTION: if a password is set on the sensor, you must first send a command to enter the password, and then the command that you need. | ATTENTION: if a password is set on the sensor, you must first send a command to enter the password, and then the command that you need. | ||