= '''Example of TD-500 sensor polling in Terminal program''' =
= '''Example of TD-500 sensor polling in Terminal program''' =
1 ответ (желтый) - ответ на запрос по протоколу LLS
1 response - response to a request via LLS protocol


2 ответ (красный) - ответ на запрос  по протоколу ModBUS RTU
2 response - response to a request via ModBUS RTU protocol


Опрос ТД-500 в программе Terminal
TD-500 polling in the Terminal program


'''$01$03$00$00$00$04$44$09''' Команда на опрос датчика по протоколу Modbus RTU (в красной рамке)
$01$03$00$00$00$04$44$09 Command to poll a sensor via Modbus RTU protocol


* 01 Сетевой адрес датчика
* 01 Sensor network address
* 03 запрашиваемая команда на чтение регистров
* 03 Requested command to read registers
* 00 00 регистр, начиная с которого запрашиваются данные
* 00 00 Register starting from which data is requested
* 00 04 количество запрашиваемых регистров
* 00 04 Number of requested registers
* 44 09 контрольная сумма CRC-16 MODBUS
* 44 09 CRC-16 MODBUS checksum


Если указать другой сетевой адрес, то нужно пересчитать контрольную сумму. Но менять сетевой адрес смысла нет, т.к. датчик будет отвечать на любой сетевой адрес.
If you specify a different network address, you need to recalculate the checksum. But there is no point in changing the network address, since the sensor will respond to any network address.


== '''Checksum calculation''' ==
== '''Checksum calculation''' ==

Revision as of 10:05, 9 December 2024

Description of MODBUS registers for TD-500

Port settings

Baud rate: 19200 kbps

Data size: 8

Stop-bits: 1

Parity: None

Request and response structure

REQUEST :

  •        (u8) Network address
  •        (u8) 0х03 --> Read command
  •        (u8) Low byte of read reg. (value is ignored)
  •        (u8) High byte of read reg. (value is ignored)
  •        (u8) Low byte of the quantity -|-|-|-|
  •        (u8) High byte of quantity -|-|-|-|
  •        (u8) CRC16 - low byte
  •        (u8) CRC16 - high byte

RESPONSE:

  •        (u8) Network address
  •        (u8) Confirmation of the command (always 0х03)
  •        (u8) Количество выгружаемых байт (always 0x08)
  •   (s8) Temperature
  •        (u8) High byte of Level
  •        (u8) Low byte of Level
  •        (u8) Always 0
  •        (u8) Always 0
  •        (u8) Always 0
  •        (u8) Always 0
  •        (u8) Always 0
  •        (u8) CRC16 - low byte
  •        (u8) CRC16 - high byte

s8 means the value is a signed integer, u8 means an unsigned integer.

Numbered addresses of the response bytes:

Byte ordinal number Byte ordinal number starting from 0 Meaning
1 0 Temperature
2 1 High byte of Level
3 2 Low byte of Level
4 3 Always 0
5 4 Always 0
6 5 Always 0
7 6 Always 0
8 7 Always 0

Baudrate does not change.

19200, 8, n, 1

The number of bits in the package is 12x8, i.e. about 96 pcs

The network number specified in the request is not important, and the number of requested registers is also not important. The main thing is that the checksum matches. The checksum calculation is given below.

Example of TD-500 sensor polling in Terminal program

1 response - response to a request via LLS protocol

2 response - response to a request via ModBUS RTU protocol

TD-500 polling in the Terminal program

$01$03$00$00$00$04$44$09 Command to poll a sensor via Modbus RTU protocol

  • 01 Sensor network address
  • 03 Requested command to read registers
  • 00 00 Register starting from which data is requested
  • 00 04 Number of requested registers
  • 44 09 CRC-16 MODBUS checksum

If you specify a different network address, you need to recalculate the checksum. But there is no point in changing the network address, since the sensor will respond to any network address.

Checksum calculation

Для того, чтобы посчитать контрольную сумму, вы можете перейти на сайт https://crccalc.com и ввести ваш запрос без знака $, выбрать HEX, CRC-16 ModBUS и нажать Calc CRC-16

Расчет контрольной суммы на сайте crccalc

Полученной значение надо записать в отправляемую команду. При этом полученное при расчете значение 0C 44 следует записать в команду как 44 0C. Обратите внимание на раскладку вашей клавиатуры. Набирать команду следует латиницей.

Response from the sensor:

01 03 08 14 04 67 00 00 00 00 00 D8 FF

  • 01 - сетевой адрес
  • 03 - команда, на которую датчик отвечает
  • 08 - количество байтов в ответе
  • 14 - температура HEX (20°C в DEC)
  • 04 67 - байты уровня Big Endian HEX (в прямом порядке) (или 1127 единиц в DEC)
  • 00 00 00 00 00 - резерв 5 байтов, не используется
  • D8 FF - CRC-16 ModBUS контрольная сумма Little Endian HEX (Обратный порядок, т.е. FF D8)